Air Cooled Built-In Water Tank Chillers |
GOOD VALUE chillers arrevedORION has not just energy saving and high precision control chiller. |
SHIPMENT FROM THAI FACTORY WITHIN 1 DAY
AT THE SHORTEST
ORION's global service network lets you free
from the unexpected shut-down of production line and equipment.
Air cooled / Water cooled | Air Cooled | ||||||||||
Series | RKS-JM | RKS-J | RKE | AKL | |||||||
Operation control method | Electric expansion value capacity control | Compressor ON/OFF control | Inverter control | Hot gas bypass control | |||||||
Model | RKS 402J-MV -00000 | RKS 752J-MV -00000 | RKS 1502J-MV -00000 | RKS 753J-V -00000 | RKS 1503J-V -00000 | RKE2200B1 -V-G2 | AKL 3750A-V | AKL 5500A-V | AKL 7500A-V | ||
Compressor output | HP (50Hz) |
0.8 | 1 | 1.6 | 1.1 | 2.4 | 2.3 | 4.0 | 8.7 | 12.3 | |
Cooling Capacity | kW (50Hz) |
1.1 | 1.8 | 3.7 | 1.8 | 4.1 | 8.7 | 12 | 20 | 25 | |
TR (50Hz) |
0.3 | 0.5 | 1.1 | 0.5 | 1.2 | 2.5 | 3.4 | 5.7 | 7.1 | ||
BTU/h (50Hz) |
3,700 | 6,100 | 12,600 | 6,100 | 13,900 | 29,600 | 40,900 | 68,200 | 85,300 | ||
Control Precision | ℃ | ±0.1 | ±2.0 | ±0.1 | ±1.0 | ||||||
Operable Liquid Temp. Range | ℃ | 5 - 40 | 15 - 35 | 5 - 35 | 10 - 30 | ||||||
Operating Pressure Range | MPa | 0.05 - 0.30 | 0.10 - 0.60 | 0.05 - 0.20 | 0.10 - 0.50 | 0.15 - 0.50 | 0.10 - 0.50 | 0.28 - 0.50 | 0.10 - 0.50 | ||
Operating Flow Rate | L/min (50Hz) |
10 - 28 | 18 - 41 | 10 - 22 | 12 - 34 | 28 - 50 | 20 - 70 | 68 - 120 | 70 - 150 | ||
Ambient Temp. | ℃ | 5 - 45 | 10 - 40 | -5 - 43 | 5 - 43 | 5 - 38 | |||||
Water Tank Capacity | L | Aprrox.17 | Aprrox.20 | Aprrox.95 | Aprrox.115 | Aprrox.140 | |||||
Power source | V(Hz) | Single-phase 200~230±10% (50/60) |
Three-phase 200±10% (50/60), 220 (60) |
Three-phase 380±10% (50) |
※ Rated condition: Chilled water temp. 20℃, Ambient temp. 32℃, Cooling capacity is at least 95% of listed figures.